An ideal Y-Y transformer, grounded through neutral impedances, displays per-unit sequence networks akin to those of a single-phase ideal transformer when subjected to balanced positive- or negative-sequence currents. These currents do not produce neutral currents, and their associated voltage drops.
Zero-sequence currents, which are identical in magnitude and phase, generate a neutral current, resulting in voltage drops across the neutral impedance and the low-voltage winding. If the transformer's neutral is ungrounded, zero-sequence currents cannot flow to the ground but can still circulate within the windings.
Practical Y-Y transformers' per-unit sequence networks incorporate external impedances. Their shunt branches represent a balanced-Y impedance load, with each phase corresponding to a core loss resistor parallel to the magnetizing inductance. These transformers possess identical per-unit positive- and negative-sequence impedances, whereas the neutral impedances influence the zero-sequence network.
Delta-delta transformers feature per-unit sequence networks with identical positive- and negative-sequence impedances. However, different winding connections can influence these impedances in practical transformers. Per-unit sequence models of three-phase, three-winding transformers can be constructed by connecting three identical single-phase transformers, using a common S-base for terminals and proportional voltage bases.
In the general zero-sequence network, the configuration of the high-voltage windings dictates the high-voltage connection. Per-unit negative-sequence network impedances always match the positive-sequence network impedances.
Do Capítulo 29:
Now Playing
Symmetrical and Unsymmetrical Faults
59 Visualizações
Symmetrical and Unsymmetrical Faults
70 Visualizações
Symmetrical and Unsymmetrical Faults
94 Visualizações
Symmetrical and Unsymmetrical Faults
55 Visualizações
Symmetrical and Unsymmetrical Faults
75 Visualizações
Symmetrical and Unsymmetrical Faults
65 Visualizações
Symmetrical and Unsymmetrical Faults
72 Visualizações
Symmetrical and Unsymmetrical Faults
53 Visualizações
Copyright © 2025 MyJoVE Corporation. Todos os direitos reservados